UPS
- 10kVA – 300kVA, 3Φ / 3Φ, 3Φ / 1Φ, 1Φ / 1Φ systems
- AC Input 415 V AC, 3Φ
- True Online Double Conversion technology
- Hot Swappable 4.4kW Fan Cooled Rectifiers
- Unique failsafe TSI System topology for continuous operation
- High efficiency Modular Topology ( Switched Mode )
- Simple Battery Replacement without disruption to load
- LCD touch-screen user interface
- Remote Monitoring with integrated SNMP Modbus, Profibus
- High reliability CAN bus communication
- User definable alarms and data logging
- Flexible Battery management & Temperature compensation
- High Output Power Factor diminishes need for UPS oversizing
- Excellent Short Circuit Protection, DC and AC Distribution
- Wide Input Voltage window minimising Battery usage
- All equipments are front accessible
- TSI inhibits Static Bypass switches & reduces Rectifier size
- Space Heaters / Fan’s with monitoring
- Batteries incorporated depending on Autonomy & Load details
- Low Voltage Disconnect (LVD) & Auxiliary contacts
- Remote Monitoring, Battery Cell Monitoring (BCM)
- High Overload capacity, 110% permanent , 150% for 15sec
- Shunt trip circuitry for remote disconnection of battery
- High Efficiency at Full and Partial Load
- Galvanic Isolation through external Transformer cabinets
Product Overview
The UPS system is a True Online Double Conversion technology designed for maximum site flexibility in a 19inch rack-mountable cabinet. UPS is highly reliable and can be configured depending on the customer requirements. The open design provides complete adaptability and flexibility to perform in a heavy Industrial environment/ application. A typical UPS system comprises a number of inverters, rectifiers, depending on the power requirement, a static transfer switch, controller and power distribution board (AC or/and DC). In addition, batteries can be incorporated in a single cabinet, to provide an effective integrated power system, depending on autonomy and load requirements.
Electrical Features
DC Input Specifications:
- Nominal Voltage ( DC ) : 110 V
- Voltage Range ( DC ) : 90 – 60 V
- Nominal Current ( at 110Vdc, 2000W O/P ) : 19 A
- Maximum Input Current ( For 15 sec ) : 29 A Input Voltage Boundaries are User Selectable.
AC Input Specifications:
- Nominal Voltage ( AC ) : 230 V
- Voltage Range ( AC ) : 150 – 265 V, 1784 W @ 150 V
- Power factor : >99%
- Synchronization : 47-53 Hz, 57-63 Hz
AC Output Specifications:
- Nominal Voltage ( AC ) : 230 V
- Voltage range ( AC ) & its Accuracy : 200 -240 V @ 2%
- Frequency & its Accuracy : 50-60 Hz @ 0.03%
- Total Harmonic Distortion ( Resistive Load ) : <1.5%
- Load Impact Recovery time : 0.4 ms
- Turn On Delay : 20 sec
- Nominal Current (protected against Reverse ) : 10.9 A
- Crest factor at Nominal Power : 3.1
- Short Circuit Clear Up capacity 10 x In for 20 msec
- Short Circuit Current after Clear up capacity : 2.1 In
- Short Circuit Current after 15 sec : 1.5 In
AC Output Power:
- Nominal Output Power : 2500 VA
- Output Power ( Resistive Load ) : 2000 W
- Short Time Overload Capacity : 150% for 15sec
- Permanent Overload capacity : 110%
- Admissible Load PF : Full Power rating, from 0 ( inductive ) to 0 ( capacitive )
- Internal Temperature management and Switch off.
- Transfer Performance :
Maximum Voltage Interruption : 0 sec
Total Transient Voltage Duration ( max ) : 0 sec
Safety & Environmental Standards
Safety | UL 60950-1 1st Edition CE marked IEC 60950 ( 1999 ) |
EMC | ETSI EN 300 386 V1.2.1 ( 2000 ) |
Power Systems | AS 4044, Type 1 to Type 4 |
Temperature Working | – 25°C – 70°C |
Storage | -25°C – 60°C |
Humidity | 0 to 100% RH condensing |
Cooling | Forced convection cooling |
Isolation | AC-DC: 2000Vrms
DC-ground: 2000Vrms AC-ground: 2000Vrms |
IP ratings | IP21, IP31, IP41, IP54 |
Electrical Wiring | AS 3000 |
UPS | AS 62040 |
Applications
- Oil & Gas.
- Power Transmission / Generation / Utilities.
- Mining
- Railways Tr/ ansportation
- Process Control
- Water
- Chemical Processing
- Renewable Energy..
Mechanical (Cabinet) Features
Dimensions (mm) | : 2200H x 800W x 800D (45RU) |
Weight | : 120kgs ( empty) |
Battery Trays | 200 – 260 kgs (Approx) |